MAGLINK LX
Configuration Manual | "Admin" Pages
Rev. 09,
– April 2016
Page 14 of 28
8
T
HE
"A
DMIN
"
PAGE
8.1
System
The following image shows the "Systems Page":
The page displays system information and parameters applied to all connected probes. The following table
lists the parameters that can be set:
Parameter Description
Total tanks Number of connected probes (From 1 to 32)
Total dispensers Number of connected dispensers (From 1 to 32)
Total Slaves (Reserved for future use)
Sensors (Reserved for future use)
Protocol Type
Select from among the following:
• DIALOG
• DOMS
• FUEL POS
• GILBARCO
• ORPAK
• PIGNONE
• RETALIX
• Probe emulation
TCP Port Gilbarco protocol via TCP
Temperature of comp.
volume
Selectable values for the calculation of the compensated volume:
• 15 °C • 20 °C
Station name Station name
History range
Time interval between a history saving data
ATTENTION: It is highly recommended to set the value to 1 minute
Probe sensitivity
Allow setting the value to 0.5
ATTENTION: Do not change unless instructed by Start Italiana S.r.l.
Language Select the language of the console display
Measurement unit
Select from among the following:
• mm/litre • inches/gallon • mm/gallon
Date format
Select from the following date formats:
• yyyy-MM-dd • dd-MM-yyyy • MM-dd-yyyy
Auto Print
Select when to perform the following automatic stamp:
• Shift report, at the beginning and end
• Alarms, at every status change
• Delivery, at the beginning and end
• Losses, upon detection of a loss
• Reconciliation, set the "Time" for reconciliation