8.12
Modem configuration settings
As option is possible to insert a GSM modem card . It is possible to receive automatic notification or texting
an SMS to the modem it will reply with the stock.
Phone number configuration for SMS
It is possible to select up to 3 telephone numbers to which address the following alert messages:
console startup
delivery parameter
leakage parameter
change tank status (alarms H, HH, L, LL, Water) both for enabled and disabled alarms
IMPORTANT!: write the mobile phone number complete of the area code without spaces.
Example: +393331234567 or 00393331234567
Connection of the GSM modem
Basic operations:
1. Disable the PIN code from the SIM card before insert it into the modem.
2. Insert the SIM card into the dedicated slot of the modem
3. Power on the console and wait some time to allow to the modem to connect to the
GSM network. When connected the GSM signal depth will appear on the display of
the console.
The GSM modem will automatically send the alarm messages listed above when occur.
Sending SMS to the console
The text of the message sent to the console must include only 3 characters.
Important:
Always write “T” in capital letter
Always write “0” before the number of the tank from 1 to 9 (for example 01 for tank 1)
T00:
shows the status of all connected tanks.
Txx:
xx refers to the number of the tank (for example T01) and shows the status of a specific tank.
The console will answer to this message showing the
reported values.