Manual of instructions TT-390 30/35
The required temperature
will not be reached,
heating lamp on the
controller lights
Solenoid valve of the
water cooling system
not closed or defective
Maybe to big consumer
Heating defective
Contactor of heating
defective
Clean the solenoid valve,
check signal to valve and
function, repair or replace it
Contact the supplier
Measure resistance of
heating
Replace contactor
Lamp „cooling“ lights, unit
is not cooling
Cooling water inlet or
outlet is closed
Filter is dirty
Solenoid valve
defective
Check water supply
check counter pressure on
cooling water outlet
Clean filter
Check solenoid valve