EasyManua.ls Logo

Toshiba ESTIA HWS-455XWHM3-E - Electrical Wiring and Connections

Toshiba ESTIA HWS-455XWHM3-E
250 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
–21–
Hydro Unit
Installation Manual
Electrical supply/cable specifications
Wiring specifications
Wiring specifications (control line)
Description
Model name
HWS-
POWER
SUPPLY
Maximum
current
Installation
fuse rating
Power wire Connection destination
Outdoor
unit
power
Power
input
1405H-E
220-230 V ~
50 Hz
22.8 A 25 A 2.5 mm² or more
,
1105H-E
220-230 V ~
50 Hz
22.8 A 25 A 2.5 mm² or more
805H-E
220-230 V ~
50 Hz
19.2 A 20 A 2.5 mm² or more
455H-E
220-230 V ~
50 Hz
11.1 A 15 A 1.5 mm² or more
1605H8-E,
1605H8R-E
380-400 V 3N~
50 Hz
14.6 A 16 A 2.5 mm² or more
, ,
,
1405H8-E,
1405H8R-E
380-400 V 3N~
50 Hz
14.6 A 16 A 2.5 mm² or more
1105H8-E,
1105H8R-E
380-400 V 3N~
50 Hz
14.6 A 16 A 2.5 mm² or more
Hydro
inlet
heater
power
Power
input for
backup
heater
1405XWHM3-E
220-230 V ~
50 Hz
13 A 16 A 1.5 mm² or more ,
TB02
1405XWHT6-E
380-400 V 3N~
50 Hz
13 A(13 A x 2P) 16 A 1.5 mm² or more
, ,
,
1405XWHT9-E
380-400 V 3N~
50 Hz
13 A(13 A x 3P) 16 A 1.5 mm² or more
805XWHM3-E
220-230 V ~
50 Hz
13 A 16 A 1.5 mm² or more
,
805XWHT6-E
380-400 V 3N~
50 Hz
13 A(13 A x 2P) 16 A 1.5 mm² or more
, ,
,
805XWHT9-E
380-400 V 3N~
50 Hz
13 A(13 A x 3P) 16 A 1.5 mm² or more
455XWHM3-E
220-230 V ~
50 Hz
13 A 16 A 1.5 mm² or more
,
Power input for cylinder
heater
220-230 V ~
50 Hz
12 A 16 A 1.5 mm² or more
,
TB03
Outdoor-Hydro unit Connection 1.5 mm² or more , , TB01
Hydro -Cylinder Connection 1.5 mm² or more , TB03
Description Line spec
Maximum
current
Maximum length
Connection
destination
3-way valve control 2 line or 3 line 100 mA 12 m 0.75 mm² or more
, ,
(TB05)
2-way valve control 2 line 100 mA 12 m 0.75 mm² or more , (TB05)
Mixing valve control 3 line 100 mA 12 m 0.75 mm² or more
, ,
or
, ,
(TB04)
2-zone thermo sensor 2 line 100 mA 5 m 0.75 mm² or more , (TB06)
Cylinder thermo sensor
2+GND(shielded
wire)
100 mA 5 m 0.75 mm² or more , (TB06)
Second remote controller 2 line 50 mA 50 m 0.5 mm² or more , (TB07)
Group control (total) 2 line 50 mA 50 m 0.5 mm² or more , (TB07)
Open protocol interface 2 line 100 mA 50 m 0.5 mm² or more , (TB07)