–24–
Hydro Unit
Installation Manual
EN
Electrical connection for external booster
heater
CAUTION
The maximum current available from the
booster heater output is 1
A. Do not connect
the booster heater directly to Terminal Block
05 on the Hydro Unit. A separate contactor,
supplied locally, must be used to supply the
booster heater.
The booster heater can be installed only for room
heating and cannot be used for hot water supply.
Install the booster heater downstream of the 3-way
valve on the indoor unit side.
The booster heater is an external heater, supplied
locally, used to assist the Hydro Unit during low
ambient conditions.
The AC230
V 1 A output from the Hydro Unit must only
be used to energize an external contactor. (Supplied
locally)
The output from the Hydro Unit is only enabled when
the outdoor air temperature is less than -20 °C.
Ensure the external booster heater is installed and set
up in accordance with all Local, National and
International regulations.
Connect the external booster heater to the Hydro
Unit in accordance with the diagram shown below.
Connect the coil, of the field supplied contactor, to
terminals 5 & 6 on Terminal Block 05. The contactor
will energize in the event of low ambient conditions.
A separate dedicated electrical supply must be used
for the external booster heater. This must be
connected through the contacts on the field supplied
contactor.
Fig. 7-23
Electrical connection for external additional
pumps
The Hydro Unit has the facility to connect an
additional circulating pump, if required, into the
heating or cooling system.
There is an output available from the Hydro Unit.
AC230 V 1 A (maximum) is available from each
output. The output for each additional pump is
synchronized with the operation of the main
circulating pump inside the Hydro Unit.
Connect the additional pumps as shown in the
diagram below.
Connect external pump 1 to terminals 1 & 2 on
Terminal Block 05.
Install external pumps so that their motive power
does not affect the internal pump.
Fig. 7-24
1234567 8 9
Terminal Block 05
Booster Heater
1234567 8 9
01
Terminal Block 05
Pump
24-EN