1
Configuring Local / Remote operations
Introduction
Local/Remote Key – Toggles between the Local and Remote modes. The LED is on when the
system is in the Local mode.
The Local mode allows the Command and Frequency control functions to be carried out via the
EOI.
The Remote mode enables the Command and Frequency control functions to be carried out via the
Control Terminal Strip, LED Keypad, RS232/485, Communication card or Pulse Input.
The availablity of the Local mode of operation may be disabled via Program
⇒
EOI Option Setup
⇒
Local/Remote Key. Here you have the option of selecting Command Mode or Frequency Mode.
The availability of the Local mode of operation may be reinstated by changing this setting, performing
a Reset, or powering down.
EOI
Command Mode Selection Program
⇒
Fundamental Parameters
⇒
Standard Mode Set
Direct Access Number – F003
Parameter Type – Selection List
Factory Default – Use Control Terminal Strip
Changeable During Run – No
The Command Mode selection establishes the source of the command inputs. Command inputs
include Run, Stop, Forward, etc.
* For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192
4
efesotomasyon.com -Toshiba inverter,drive,servo,plc