H7 ASD Operation Manual 181
EPH O Output Line Loss This fault occurs when one
or more of the output power
lines from the ASD are
inactive or missing.
Output power line from the
ASD is not connected to the
motor.
•A U, V, or W fuse is open
(blown).
•A U, V, or W contactor is
open.
•A U, V, or W HCT is
defective.
Ensure that the motor
leads are connected
properly and securely.
Measure the individual
running current of the U,
V, and W leads (no
current = problem line).
ERR2 Main RAM Fault This fault is caused by
corrupted RAM data or an
inability to read the RAM
data.
Defective RAM. Make a service call.
ERR3 Main ROM Fault This fault is caused by
corrupted ROM data or an
inability to read the ROM
data.
Defective ROM. Make a service call.
ERR4 CPU Fault This fault is caused by a
CPU malfunction.
Defective CPU. Make a service call.
ERR5 Communication
Interruption Fault
This fault is caused by an
inability of the ASD to
communicate with an
optional device or another
ASD in a master/follower
configuration.
Corrupted data at the master
ASD.
Broken or improper
connections associated with
the setup.
Improper setup information
at the follower device.
Ensure that the master
ASD is programmed
properly.
Ensure that the
connections are correct
and secured.
Confirm all
communications settings.
ERR6 Gate Array Fault This fault results when a
given input to the gate array
results in an unexpected
output.
Gate array output
discrepancy.
Defective gate array.
Make a service call.
ERR7 Output Current
Detector Error
This fault occurs when the
output current of the ASD
exceeds the established
parameters for a given
application or configuration.
Defective HCT. Make a service call.
ERR8 Option Device
Fault
This fault is caused by a
malfunction in one of the
ASD option devices.
Defective option device.
Option device is not
connected securely.
Option device is not
configured correctly.
Replace the defective
option device.
Ensure that the
connections are correct
and secured.
Ensure that the option
device is configured
correctly.
ERR9 Flash Memory
Fault
This fault is caused by
corrupted data in the flash
source or destination
memory location.
Defective flash memory
(ROM or RAM).
Make a service call.
EOI
Display
Function Description Possible Causes Corrective Action