204 Appendix D H7 ASD Operation Manual
Table 13. 600 Volt NEMA Type-1 Chassis standard ratings table.
Model
VT130H7U
Rated
KVA
Motor
HP/Kw
Input Voltage
3-Ph 50/60
± 2 Hz
Output Voltage
3-Ph Variable
Frequency
Output Current
100%
Continuous
Overload
Current 120% for
60 Secs.
6035 3.50 3.00/2.24
495 – 600 VAC
(+5/-10%)
Input Voltage Level
(Max.)
4.00 A 4.8 A
6060 6.00 5.00/3.73 6.1 A 7.3 A
6080 8.00 7.50/5.60 9.0 A 10.8 A
6120 12.0 10.0/7.46 12.0 A 14.4 A
6160 16.0 15.0/11.2 17.0 A 20.4 A
6220 22.0 20.0/14.9
495 – 600 VAC
(±10%)
22.0 A 26.4 A
6270 27.0 25.0/18.6 27.0 A 32.4 A
6330 33.0 30.0/22.4 32.0 A 38.4 A
6400 40.0 40.0/30.0 41.0 A 49.2 A
6500 50.0 50.0/37.0 52.0 A 62.4 A
6600 60.0 60.0/45.0 62.0 A 74.4 A
6750 75.0 75.0/55.0 77.0 A 92.4 A
610K 100 100/75.0 99.0 A 118.8 A
612K 125 125/90.0 125.0 A 150.0 A
615K 150 150/110 150.0 A 180.0 A
620K 200 200/150 200.0 A 240.0 A
625K 250 250/185 250.0 A 300.0 A
630K 300 300/220 300.0 A 360.0 A
www . ElectricalPartManuals . com