– 25 –
Function CODE No. (DN Code) table (includes all functions needed to perform applied control on site)
DN Item Description At shipment
03
Central control address 0001: No.1 unit
0001: No.1 unit
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
to
to
0064: No.64 unit ... TCC-LINK
0128: No.128 unit ... TU2C-LINK
00Un/0099:
Unfixed
12
Line address 0001: No.1 unit
0001: No.1 unit
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
to
to
0064: No.30 unit ... TCC-LINK
0128: No.128 unit ... TU2C-LINK
00Un/0099:
Unfixed
0b
Demand control
(CN73)
0000: Demand input
0002: Card input setup.3
0004: Card input setup.4
0005: Fire alarm input
(Normal close)
0007: Card input setup.5
0009: Card input setup.2
0001: O2 sensor input
0002: Card input setup.3
(Normal open)
0006: Notice code (202)
0008: Card input setup.1
0000: Demand
input
13
Indoor unit address 0001: No.1 unit
0001: No.1 unit
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
to
to
0064: No.64 unit ... TCC-LINK
0128: No.128 unit ... TU2C-LINK
00Un/0099:
Unfixed
14
Group address 0000: Individual
0002: Follower unit of group
00Un: Unfixed (When using U series remote controller)
0099: Unfixed (Other than U series remote controller)
0001: Header unit of group 00Un/0099:
Unfixed
2E
HA terminal (CN061)
select
0000: Usual
0002: Fire alarm input
(Normal open)
0004: Notice code (201)
0001: Card input setup.1 (3)
0003: Card input setup.2 (4)
0005: Card input setup.5
0000: Usual
(HA terminal)
10
Type 0060: Hot Water Module
* refer to Type DN code [10]
Depending on
model type
E0
Destination 0000: Japan
0004: Global
0004: Global
11
Indoor unit capacity 0000: Unfixed
* Refer to Indoor Unit Capacity DN code [11]
0001 to 0044 Depending on
model type
FC
Communication
protocol *1
0000: TCC-LINK 0003: TU2C-LINK 0000: TCC-LINK
28
Automatic restart of
power failure
0000: None 0001: Restart 0000: None
60
Timer setting
(wired remote controller)
0000: Available
(can be performed)
0001: Unavailable
(cannot be performed)
0000: Available
1FC
Indoor Unit
terminating resistance
0000: OFF 0001: ON 0000: OFF
180
Notice code
number 01
0000: None
0001 ~ 0255 : Notice code
0129 : Notice code (201)
0130 : Notice code (202)
(0001 ~ 0255 : TU2C-LINK only)
(Refer to outdoor service manual)
0000: None
181
Notice code
number 02
0000: None
182
Notice code
number 03
0000: None
183
Notice code
number 04
0000: None
184
Notice code
number 05
0000: None
185
Notice code
number 06
0000: None
186
Notice code
number 07
0000: None
187
Notice code
number 08
0000: None
188
Notice code
number 09
0000: None
189
Notice code
number 10
0000: None
1FB
Central device control
state
0000: No central device control (Remote controller use is possible)
0001: Central device control (Remote controller use is impossible)
0000: No central
device
control