– 42 –
Note 1: Criteria for the difference between suction and discharge temperatures, between water
inlet and water outlet temperature
(1) Cooling operation
After operating for a minimum of 30 minutes in “COOL” mode, if the 'T dry bulb temperature difference
between suction and discharge air of the indoor unit is 8°C or more, it is normal.
(2) Heating operation
After operating for a minimum of 30 minutes in “HEAT” mode, if the 'T dry bulb temperature difference
between suction and discharge air of the indoor unit is 15°C or more, it is normal.
After operating for a minimum of 30 minutes in “HEAT” mode, if the 'T water temperature difference between
water inlet and water outlet of the hot water module is 3 to 5 degrees, it is normal. (Hot water module)
* If demand from the indoor unit on the outdoor unit is low because the difference between the temperature
set by the remote controller and the temperature of the room or the difference between the temperature
set by the remote controller and the water inlet temperature is small, then the 'T temperature difference is
small.
* Consider that 'T temperature difference may diminish in cases of a system in which the connected indoor
unit capacity exceeds the outdoor unit capacity, the pipe length is long, or a large difference exists among
outdoor units.
Note 2: Criteria for operating power current
The table below shows the maximum current for each outdoor unit. Under standard conditions, operating
current is about 80% of the value shown in the table below.
Note 3: Criteria for cycle status
(1) These data are based on operating a 4-way Air Discharge Cassette type air conditioner including Hot Water
Module 1 unit of 100% connection with standard piping length.
Data may vary depending on temperature conditions, installed pipe length, and room shape combinations,
or indoor unit connection capacity.
For pressure criteria in different temperature conditions, refer to (2).
<SMMS-i>
Outdoor unit MMY-MAP 0804
∗
1004
∗
1204
∗
1404
∗
1604
∗
Current value (A) 23.5 25.5 28.5 33.2 36.5
1606
∗
35.8
1806
∗
40.6
2006
∗
44.9
2206
∗
49.3
Model
Current value
MMY-MUP***HT8
(A)
0801
15.4
1001
20.5
1201
24.5
1401
27.5
1601
30.5
1801
34
2001
36
2201
51
2401
54
Compressor Compressor Compressor
123
2.9 0.9 85 15 - 10 40 40 50 50 - High 27/19 35/-
䋭
3 0.7 85 5 35 35 3 30 50 50 - High 20/- 7/6 30
3
0.8 85
15
-8
40
40 65 65 - High 27/19 35/-
䋭
3.1 0.7 85 4 35 35 2 30 65 65 - High 20/- 7/6 30
3.1 0.8 85 17 - 8 40 40 70 70 - High 27/19 35/-
䋭
3.1 0.7 90
2
35 3
5
2 30 75 75 - High 20/-
7/6
30
3 0.8 85 15 - 10 40 4
0
60 6
06
0 High 27/19
35/-
䋭
3.1 0.7 85
4
3
535
330 60 60
60 High 20/- 7/6
30
3.1 0.8 90 15 - 10 40 40 65 65 65 High 27/19 35/-
䋭
3.1 0.7 90 2 35 35 2 30 65 65 65 High 20/- 7/6 30
Indoor
fan
Outdoor
Inlet water
temperature
(°C)
TWI (TA)
Hot water
module
TWO (TC2)
*2
Outdoor
unit
MMY-
MAP
Pressure
(MPa)
PsPd
Air temperature
condition
(DB/WB) (°C)
Number of compressor rotations
(rps)*1
Pipe surface temperature
(°C)
Liquid
temperatre
(TL)
Indoor
1604*
1404*
1204*
1004*
0804*
Outdoor
heat
exchanger
(TE)
Indoor heat
exchanger
(TC)*2
Suction
(TS)
Discharge
(TD)
*1 This compressor is driven with a 4-pole motor. The value of the compressor frequency (rps) measured with a clamp meter at the compressor
lead line is two times the rotation count (rps) of the compressor.
*1 Each compressor may have a different frequency as a measure against resonance.
*2 The temperature of the indoor heat exchanger (TC) indicates TCJ sensor temperature when cooling, and TWO (TC2) sensor temperature
when heatin
, res
ectivel
. And the tem
erature of the Hot Water Module indicates TWO
TC2
sensor tem
erature when heatin
onl
.
Pd Ps
Discharge
(TD)
Suction
(TS)
Indoor heat
exchager
(TC)
Outdoor heat
exchanger
(TE)
Liquid
tempreture
(TL3)
Compressor
1
Compressor
2
Indoor Outdoork
Cooling 3.2 0.9 90 16 10 40 35 70 70 High 27/19 35/-
Heating 2.8 0.7 85 3 30 2 25 70 70 High 20/- 7/6
Cooling 3.1 0.9 80 15 11 40 35 70 70 High 27/19 35/-
Heating 2.8 0.7 70 4 30 3 25 75 75 High 20/- 7/6
Cooling 3.1 0.9 85 15 11 40 35 80 80 High 27/19 35/-
Heating 2.8 0.6 75 3 30 2 25 85 85 High 20/- 7/6
Cooling 3.2 0.9 95 14 11 40 35 100 100 High 27/19 35/-
Heating 2.7 0.6 75 3 30 2 20 85 85 High 20/- 7/6
2006*
2206*
Pressure
(MPa)
1606*
1806*
Outdoor
unit
MMY-
MAP
Operating
mode
Pipe surface temperature
(㷄)
Number of compessor
rotations
(rps) *1 Indoor
fan
Air temperature
condition
(DB/WB) (㷄)
<SMMS-e>