– 44 –
(2) Criteria for operating pressure
<SMMS-i> <SMMS-e>
<SMMS-u>
* Criteria after 15 minutes or more has
assed since o
eratin
started
Operating mode Cooling Heating
Indoor temperature (˚C) 18~32
25~35
2.0~3.3
0.5~0.9
15~32
5~35
2.5~3.3
0.5~0.7
Outdoor temperature (˚C)
Pressure
High pressure (MPa)
Low pressure (MPa)
* Criteria after 14 minutes or more has
assed since o
eratin
started
Operating mode Cooling Heating
Indoor temperature (˚C) 18~32
25~35
2.0~3.3
0.5~0.9
15~32
5~35
2.5~3.3
0.5~0.7
Outdoor temperature (˚C)
Pressure
High pressure (MPa)
Low pressure (MPa)
Operating mode Cooling Heating
Indoor temperature (˚C) 18~32
25~35
2.0~3.7
0.5~0.9
15~25
5~10
2.5~3.3
0.5~0.7
Outdoor temperature (˚C)
Pressure
High pressure (MPa)
Low pressure (MPa)
(3) On rotations of outdoor fans
Outdoor fans may rotate slowly to control pressure when cooling with low outer air temperature or heating
with excessive load. For control content, also refer to service manual of outdoor unit.
<SHRM-e>
* Criteria after 15 minutes or more has
assed since o
eratin
started
Operating mode Cooling Heating
Indoor temperature (˚C) 18~32
25~35
2.0~3.3
0.5~0.9
15~25
5~10
2.5~3.3
0.5~0.7
Outdoor temperature (˚C)
Pressure
High pressure (MPa)
Low pressure (MPa)