Function CODE No. (DN Code) Table (Includes All Functions Needed to Perform Applied Control on Site)
DN Item Description At shipment
01
Filter display delay timer 0000: None
0002: 2500H
0004: 10000H
0001: 150H
0003: 5000H
According to type
02
Dirty state of filter 0000: Standard
0001: High degree of dirt (Half of standard time)
0000: Standard
03
Central control address 0001: No.1 unit
0099: Unfixed
to 0064: No.64 unit 0099: Unfixed
04
Specific indoor unit
priority
0000: No priority 0001: Priority 0000: No priority
06
Heating temp shift 0000: No shift
0002: +2°C to
0001: +1°C
0010: +10°C
(Up to +6 recommended)
0002: +2°C
(Floor type 0000: 0°C)
0d
Existence of [AUTO]
mode
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0001: Not provided
0F
Cooling only 0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0000: Heat pump
10
Type 0001: 4-way Air Discharge Cassette Depending on model
type
11
Indoor unit capacity 0000: Unfixed 0001 to 0034 According to capacity
type
12 Line address 0001: No.1 unit to 0030: No.30 unit 0099: Unfixed
13 Indoor unit address 0001: No.1 unit to 0064: No.64 unit 0099: Unfixed
14
Group address 0000: Individual
0002: Follower unit of group
0001: Header unit of group 0099: Unfixed
19
Louver type
(Air direction
adjustment)
0000: No louver 0001: Swing only According to type
0002: (1-way Air Discharge Cassette type, Under Ceiling type)
0003: (2-way Air Discharge Cassette type)
0004: (4-way Air Discharge Cassette type)
1E
Temp difference of
[AUTO] mode selection
COOL $ HEAT,
HEAT $ COOL
0000: 0 deg to 0010: 10 deg 0003: 3 deg
(Ts±1.5)
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
28
Automatic restart of
power failure
0000: None 0001: Restart 0000: None
2A
Selection of option/error
input (CN70)
0000: Filter input
0002: None
0001: Alarm input (Air washer, etc.) 0002: None
2E
HA terminal (CN61)
select
0000: Usual
0002: Fire alarm input
0001: Leaving-ON prevention control 0000: Usual
(HA terminal)
31 Ventilating fan control 0000: Unavailable 0001: Available 0000: Unavailable
32 TA sensor selection 0000: Body TA sensor 0001: Remote controller sensor 0000: Body TA sensor
33 Temperature unit select 0000: °C (at factory shipment) 0001: °F 0000: °C
F0
Swing mode 0001: Standard
0003: Cycle swing
0002: Dual swing 0001: Standard
F1
Louver fixed position
(Louver No.1)
0000: Release
0005: Downward discharge position
0001: Horizontal discharge position 0000: Not fixed
F2
Louver fixed position
(Louver No.2)
0000: Release
0005: Downward discharge position
0001: Horizontal discharge position 0000: Not fixed
F3
Louver fixed position
(Louver No.3)
0000: Release
0005: Downward discharge position
0001: Horizontal discharge position 0000: Not fixed
F4
Louver fixed position
(Louver No.4)
0000: Release
0005: Downward discharge position
0001: Horizontal discharge position 0000: Not fixed