68 Q9 ASD Installation and Operation Manual
Automatic Function Selection
No Path — Direct Access Only
This parameter setting is used to configure multiple parameters with the setting of
only one parameter. From the selection below multiple parameters may be set as
indicated in the table.
Once set, the selected configuration is placed in effect and remains in effect until
this parameter is changed or the individual settings are changed.
Set this parameter to Disable to set these parameters individually.
Note: After performing the desired selection the EOI display returns to
Disabled though the selected function has been carried out
(i.e.
, Without this, if selection 1 is performed, F004 and F207
would retain the RR terminal setting regardless of attempts to
change the settings individually).
Settings:
0 — Disabled
1 — RR
2 — V/I
3 — RR or VI/II (V/I) Switched via Terminal Board
4 — Keypad = Frequency/Terminal Board = Command
5 — Keypad = Frequency and Command
Direct Access Number — F040
Parameter Type — Selection List
Factory DefaultDisabled
Changeable During Run — No
User Settings
Related
Parameters
Default
Settings
0-Disabled 1-RR 2-V/I
3-RR or
V/I via
TB
4-Keypad/
Freq.
CMD/TB
5-Keypad
Freq/CMD
CMOD
F003
Terminal
Board
N/C
Terminal
Board
Keypad
FMOD1
F004
RR N/C RR N/C RR Keypad
S3 Terminal
F117
Preset
Speed 3
N/C
Freq.
Ref.
Priority
N/C
Freq.
Priority
F200
Terminal
Board
N/C Terminal Board
V/I Setup
F201
0.0% N/C 20.0% N/C
FMOD2
F207
V/I N/C RR V/I Keypad
N/C = No Change the setting remains as it was before setting parameter F040.
F040 F040