8-14. DRY Operation
(The remote controller’s MODE button is set to the
DRY position.)
(1) In this mode, a microprocessor control lowers hu-
midity while maintaining a constant temperature.
(2) The microprocessor turns the compressor on and
off at regular intervals (4 to 6 minutes on and/or
off). During the compressor off, the airflow fan
will operate in the ultra low position.
(3) The compressor and airflow fan will operate in-
dependent of the temperature control, though the
pattern of operation depends on the relation be-
tween room temperature (T
A
) and set tempera-
ture (T
S
), as shown below:
Fig. 8-26
Table 8-3
• The airflow fan will operate in the Low position,
independent of the position of the airflow setting
control.
8-15. AUTO Operation
(The remote controller’s MODE button is set to the
AUTO position and AUTO display is lit.)
(1) One of the 3 modes, Cooling, Fan only and Heat-
ing is selected according to room temperature at
which operation is to start, as shown in Fig. 8-27.
The Fan mode will continue until room tempera-
ture reaches a level at which another mode is
selected.
8-15-1. Temporary Auto
When the TEMPORARY switch is set to AUTO., the
set temperature is fixed at 24°C and controlled in ac-
cordance with the chart shown in Fig. 8-27.
OFF
period
a
4 min.
5 min.
6 min.
ON
period
b
6 min.
5 min.
4 min.
Relation between room
temp. (T
A
) and
set temp. (T
S
)
T
A
 > T
S
 + 2
T
S
 + 2 > T
A
 > T
S
T
S
 > T
A
Fig. 8-27
Note:
• Operation is controlled at temperature above, independent on the position of the room temperature control.
a
b
b
*
U.L. U.L. U.L. U.L.
minutes
Compressor
irflow fan
*
Ultra Low
Stop Stop
Low
Stop
Low Low
Room temperature (T
A
) measurement timing
Time
Stop
Low
Cooling mode     (The same cooling mode as when the room temperature control is
                             is set at set temp. + 1 C)
                            The Lover moved MID-SUMMER control.   
Cooling mode     (The same cooling mode as when the room temperature control is
                             is set at set temp. + 1 C)
 
Fan only mode    (Low position)
Cooling mode     (The same cooling mode as when the room temperature control is
                             is set at set temp. + 2 C)
 
+ 4
+ 1
- 1
(Room temp. - Set temp.)