– 36 –
Check
code
Table 9-5
Condition
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Indicated when
detected abnor-
mal.
Block level
Check
code
Block
Indoor PC
board
Cable
connection/
Thermal fuse
Refrigerant
system
Symptom
Thermo sensor
short/break.
Heat exchanger
sensor short/
break.
Indoor fan lock,
abnormality of
indoor fan.
Abnormality of
other indoor unit
PC board.
Thermal fuse
cut off.
Indoor fan lock,
abnormality of
indoor fan.
Gas shortage.
(gas leak)
Other refriger-
ant cycle
trouble.
Heat exchanger
sensor off/
break/short.
Overload relay
break
Air conditioner
status
Continued
operation
Continued
operation
All off.
Continued
operation
All off.
All off.
Diagnosis function
Judgement and action
Check thermo sensor.
If it is OK, check PC
board. (Around sensor
circuit)
Check heat exchanger
sensor.
If it is OK, check PC
board. (Around sensor
circuit)
Check motor.
Replace PC board, if
the same failure
occurs, after the motor
check.
Replace PC board.
Check thermal fuse.
If it is OK, check
motor.
If motor is OK, check
PC board. (12V power
circuit)
Check gas quantity.
(Check gas leakage)
If it is OK, check heat
exchanger sensor.
If heat exchanger
sensor is OK, check
overload relay.
If overload relay is OK,
check refrigerant
cycle.
If refrigerant cycle is
OK, check PC board.