FILE NO. SVM-13092
7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/- 077SKV-
E6
0.9 to 1.1 13 to 14 45 to 46 High
High 40
107SKV -E6 0.9 to 1.0 11 to 12 48 to 49 High High 53
137SKV -E6 0.8 to 1.0 10 to 11 48 to 49 High High 75
condition(°C)
Tempeature Heat exchanger
pipe temp.
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 077SKV-E6 2.4 to 2.5 36 to 37 0 to 1 High High 51
107SKV -E6 2.4 to 2.5 40 to 41 0 to 1 High High 67
137SKV -E6 2.8 to 2.9 41 to 42 0 to 1 High High 75
condition(°C)
Tempeature Heat exchanger
pipe temp.