FILE NO. SVM-02001
10-3. Outdoor Unit (RAS-13UA-E, RAS-13UAX)
1
2
3
4
Common
procedure
Capacitor for
compressor
Capacitor for fan
motor
Overload
relay
1) Stop the operation of the air-conditioner, and
disconnect the power cord from the AC supply.
2) Remove Electric parts cover.
(2-Screws 4 x 10L)
3) Remove the cord clamp (2-Screws 4 x 12L)
and disconnect the connecting cable.
4) Remove the front cabinet.
(7-Screws 4 x 10L with nylon washer)
Pull the front lower portion toward you, and
remove it pulling out upward.
1) Perform the common procedure 1.
2) Remove the fixing screw and the capacitor band.
(1-Screw 4 x 10L)
3) Disconnect the lead wires.
1) Perform the common procedure 1.
2) Remove the
fixing screw
.
(1-Screw 4 x 10L)
3) Disconnect the lead wires.
1) Perform the common procedure 1.
2) Remove the terminal cover of compressor.
3) Remove the overload relay holder and pull up
the overload relay.
4) Disconnect the lead wires.
No. Part name Procedures Remarks
2-Screws 4 x 12L
2-Screws 4 x 10L
Remove
7-Screws 4 x 10L
RAS-13UA-E
RAS-13UAX
Overload relay
For compressor
For fan motor
For fan motorFor compressor