– 69 –
FILE NO. SVM-02001
10-5. Outdoor Unit (RAS-10UA-E, RAS-10UAX-1)
No. Part name Procedures Remarks
1
2
3
4
Common
procedure
Capacitor for
compressor
Capacitor for fan
motor
Overload relay
1) Stop the operation of air-conditioner, and
disconnect the power cord from the AC supply.
2) Remove Electric parts cover.
(2-Screws 4 x 10L)
3) Remove the cord clamp (2-Screws 4 x 12L)
and disconnect the connecting cable.
4) Remove the front cabinet.
(7-Screws 4 x 10L with nylon washer)
Pull the front lower portion toward you, and
remove it pulling out upward.
1) Perform the common procedure 1.
2)
Remove the fixing screw and the capacitor band.
(1-Screw 4 x 8L)
3) Disconnect the lead wires.
1) Perform the common procedure 1.
2)
Remove the fixing screw and the capacitor band.
(1-Screw 4 x 8L)
3) Disconnect the lead wires.
RAS-10UAX-1
1) Perform the common procedure 1.
2)
Remove the fixing screw.
3) Disconnect the lead wires.
1) Perform the common procedure 1.
2) Remove the terminal cover of compressor.
3) Remove the overload relay holder and pull up
the overload relay.
4) Disconnect the lead wires.
Remove
7-Screws 4 x 10L
2-Screws 4 x 12L
2-Screws 4 x 10L
For compressor For fan motor
RAS-10UA-E
RAS-10UAX-1
For compressor For fan motor
Overload relay
RAS-10UA-E
Overload relay
RAS-10UAX-1