7-3. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U
bent.(Thermistor themometer)
2. Connecting piping condition : 7.5 m
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/-
18PKVSG-E
1.0 to 1.1
10 to 12
48 to 50
High
High
66
22PKVSG-E
1.1 to 1.2
9 to 11
49 to 51
High High
87
24PKVSG-E
1.0 to 1.1 11 to 13 49 to 52
High High
88
condition(°C)
Tempeature Heat exchanger
pipe temp.
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6
2.8 to 3.0 42 to 44
0 to 1
High High
81
2.9 to 3.1 43 to 45
0 to 1 High High
90
3.0 to 3.2 44 to 46
1 to 2
High High
98
condition(°C)
Tempeature Heat exchanger
pipe temp.
18PKVSG-E
22PKVSG-E
24PKVSG-E
FILE NO. SVM-17001