NOTE :
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
INDOOR UNIT
T1 Temp. measurement
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allowable height
difference : 12m
Allowable pipe length
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 12.70mm
Thickness : 0.8mm
Pulse Modulating
valve at liquid side
TD
4-way valve
Compressor
DX151A1T-30N
Outdoor heat
exchanger
Propeller fan
OUTDOOR UNIT
Muffler Tank
Muffler
TE
TC
TA
Max. : 25m
Min. : 2m
Chargeless : 15m
TO
Strainer
RAS-B24J2KVSG-E, RAS-B24N4KVSG-E / RAS-24J2AVSG-E
Strainer
Refrigerant amount : 1.14kg
Split capillary
T2
Temp. measurement
TS
NOTE :
The maximum pipe length of this air conditioner is 15 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
- 26 -