Item
Operation flow and applicable data, etc.
Description
17. QUIET
M
ode
Quiet mode is the system which, control the
revolving speed of indoor fan to work
constantly at lower than speed L. In addition,
noise level of indoor unit is less than usual.
Remarks :
The "Quiet mode" selected from [ FAN ] button;
- The fan of the indoor unit will be restricted the
revolving speed at speed UL.
- The compressor speed is controlled as shown in
the figure.
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less
cooling load condition.
Because of the fan speed L- may cause not
enough the cooling capacity capacity.
18. Short Timer
In the normal condition, after switching one circuit
breaker, 3-minute delay time for compressor and
1 hour for plasma air purifier are set for the
maintenance of the unit.
Purpose
To start the unit immediately for the purpose of
testing, trial...etc, short timer can be used.
maintenance of the unit.
Short Timer Setting
1 Press [ ] button to turn the unit OFF.
2 Set the operation mode
on the remote control without
sending the signal to the unit.
3 Use the tip of the pencil to push the
[CHECK] button and hold, "00" will
show on display, them press [SET]
button to make "00" disappear.
4 Press [ ] button to turn the unit ON.
5 When short timer is activated, all
setting on the remote operates
immediately, besides, all indicatiors
on front panel turns ON continuously
for 3 seconds.
The "Quiet mode" is canceled by [ FAN ] button is
pressed to select other speed.
Model 18k 22k 24k
Cool min (Hz) 19.2 19.2 19.2
Quiet Cool (Hz) 44.4 44.4 44.4
Heat min (Hz) 19.2 19.2 19.2
Quiet Heat (Hz) 55.2 55.2 55.2
3
4