7-3. Operation Data
<Cooling>
<Heating>
NOTES :
Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor thermometer)
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
B22J2KVSG-E
B22N4KVSG-E
1.1 to 1.2
9 to 11
49 to 51
High High
87
B24J2KVSG-E
B24N4KVSG-E
1.0 to 1.1 11 to 13 49 to 52
High High
88
condition(°C)
Tempeature Heat exchanger
pipe temp.
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
2.9 to 3.1 43 to 45
0 to 1 High High
90
3.0 to 3.2 44 to 46
1 to 2
High High
98
condition(°C)
Tempeature Heat exchanger
pipe temp.
B22J2KVSG-E
B22N4KVSG-E
B24J2KVSG-E
B24N4KVSG-E
Connecting
piping
(m)
Connecting
piping
(m)
7.5
27/19 35/-
18J2KVSG-E
18N4KVSG-E
1.0 to 1.1
10 to 12
48 to 50
High High
66
7.5
2.8 to 3.0 42 to 44
0 to 1 High High
78
18J2KVSG-E
18N4KVSG-E
27/19 35/-