– 19 –
FILE NO. SVM-01010
7-2-4. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 2 operations (Cooling or Fan only) is
selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-6. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in Fig.
7-2-6.
Fig. 7-2-6
+4
0
(Room temp.) – (Preset temp.)
°C
Cooling operation
The louver moves to the position
same as Hi Power operation.
Cooling operation
Fan only operation
RAS-24UKX, RAS-24UK-AR
RAS-18UKX,RAS-18UK-AR
7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, outdoor fan and operation display
on the remote control are controlled as shown in
Fig. 7-2-4.
Fig. 7-2-4
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset tempera-
tures is shown in Fig. 7-2-5.
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECONO. operations can not be set.
(Room temp.) – (Preset temp.)
Preset
temp.
ON
+3
+2
+1
0
OFF
Outdoor fan
OPERATION
display
Compressor
Common relay
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
ON
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
L.
*
S.L. S.L.L. L. S.L. L.
ON ON ON ON
OFF OFF OFF
*
Super Low