– 3 –
FILE NO. SVM-01010
ITEM
MODEL
RAS-24UKX/24UAX
RAS-24UK-AR/24UA-AR RAS-18UKX/18UAX RAS-18UK-AR/18UA-AR
Cooling Cooling Cooling Cooling
Capacity kW
220V 240V 220V 240V 220V 240V 220V 240V
6.40 6.45 6.40 6.45 5.20 5.25 5.20 5.25
Phase
1Ø
V
220-240
Hz 50
Power consumption W 2350 2440 2350 2440 1870 1950 1920 2040
Power factor % 96 91 96 91 95 88 95 88
Running 220V 240V 220V 240V 220V 240V 220V 240V
current Indoor /Outdoor A 0.3/10.9 0.3/10.8 0.3/10.9 0.3/10.8 0.2/8.75 0.2/9.0 0.2/9.0 0.2/9.5
Starting current A 50 40
Moisture removal lit/h 2.7 2
Noise
Indoor (H/M/L) dB 45/41/37 42/39/35
Outdoor (220-240V) dB 56-57 51 52 52 53
Refrigerant
Name of refrigerant R22
Rated amount kg 1.63 1.06 1.17
Refrigerant control Capillary tube
Gas side size mm Ø 15.88 Ø 12.7
Connection type Flare connection
Liquid side size mm Ø 6.35
Connection type Flare connection
Maximum length
m
15*
1
(One way) 25*
2
20*
2
Maximum height
m10 8
difference
INDOOR UNIT RAS-24UKX RAS-24UK-AR RAS-18UKX RAS-18UK-AR
Height mm 298
Dimensions Width mm 998
Depth mm 208
Net weight kg 12
Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m
3
/h 950 750
Air volume Medium fan m
3
/h 750 650
Low fan m
3
/h 600 530
Fan motor output W 30
Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-24UAX RAS-24UA-AR RAS-18UAX RAS-18UA-AR
Height mm 690 538
Dimensions Width mm 880 830
Depth mm 310 300
Net weight kg 65 65 50 54
Condenser type Finned tube
Outdoor fan type Propeller fan
Airflow volume m
3
/h 3380 3560 3380 3560 1830 2010 2105 2310
Fan motor output W 65 65 42 65
Compressor Model PH280X3-4MS PH250X3-4LM
Output W 2000 1500
Safety device IOL
Louver type Automatic louver
Usable outdoor temperature range °C 15 ~ 43 15 ~ 52 15 ~ 43 15 ~ 52
Interconnection
pipe
Power source
1. SPECIFICATIONS