42
FILE NO. SVM-01010
[0C Indoor TA sensor error]
[0d Indoor TC sensor error]
Is CN04 (TA sensor connector)
connected properly?
YES
NO
YES
NO
Is TA sensor resistance value
(10 k at 25°C) normal?
Indoor P.C. board is defective.
Replace
TA sensor.
Replace
P.C. board.
Connect CN04
properly.
Is CN05 (TC sensor connector)
connected properly?
YES
NO
YES
NO
Is TC sensor resistance value
(10 k at 25°C) normal?
Indoor P.C. board is defective.
Replace
TC sensor.
Replace
P.C. board.
Connect CN05
properly.