INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
Part
code
Parts name Q’ty
A
Refrigerant piping
Liquid side  :  Ø6.35 mm
Gas side  :  Ø9.52 mm
 (RAS-B10N4KVRG-E1)
 (RAS-B13N4KVRG-E)
 : Ø12.70 mm
 (RAS-B16N4KVRG-E)
One
each
B
Pipe insulating material
(polyethylene foam, 6 mm thick)
1
C
Putty, PVC tapes
One
each
Optional Installation Parts
Insulate the refrigerant pipes separately 
with insulation, not together.
6 mm thick heat resisting 
polyethylene foam
3
Batteries
7
Flat head
wood screw
4
Remote controller 
holder
Vinyl tape
Apply after carrying
out a drainage test.
2
Wireless
remote controller
Saddle
Extension drain hose
(Not available, provided 
by installer)
Shield pipe
(Attach to the front panel.)
Air fi lter
Hook
Hook
Hook
1
Installation
plate
5
Filter
6
Mounting
screw
Cut out a piece of SPACER from indoor
unit packaging box, roll it and insert
between the indoor unit and wall to tilt
the indoor unit for better operation.
For the rear left and bottom left piping
Wall
The auxiliary piping can be connected
to rear left, rear right, bottom right or 
bottom left.
Bottom left
Bottom
right
Rear
left
Rear
right
Make sure to run the drain hose sloped 
downward.
Do not allow the drain hose to get slack.
Cut the piping 
hole sloped 
slightly.
Refrigerant piping must be protected 
from physical damage.
Install a plastic cover or equivalent.
100 mm or more
erom ro mm 006
600 mm or more
100 mm or more
600 mm or more
300 mm or more
73 mm or more
350 mm or more
  Secure the outdoor unit with fi xing bolts and nuts if the unit is likely to be 
exposed to a strong wind.
  Use Ø8 mm or Ø10 mm anchor bolts and nuts.
  If it is necessary to drain the defrost water, attach drain nipple % and cap 
water proof & to the bottom plate of the outdoor unit before installing it.
Fixing bolt arrangement of outdoor unit
 When using a multi-system outdoor unit, refer to the installation manual 
provided with the model concerned.
2