Model
RAS-10J2AVSG-E1 RAS-13J2AVSG-E1 RAS-16J2AVSG-E1
Chargeless up to 15 m up to 15 m up to 15 m
Maximum length 20 m 20 m 20 m
Additional refrigerant 
charging
16 - 20 m
(20 g / 1 m)
16 - 20 m
(20 g / 1 m)
16 - 20 m
(20 g / 1 m)
Maximum refrigerant 
charging
0.65 kg 0.90 kg 0.90 kg
  The allowable height of outdoor unit installation site.
Model
RAS-10J2AVSG-E1 RAS-13J2AVSG-E1 RAS-16J2AVSG-E1
Maximum height 12 m 12 m 12 m
  A place where the drain water does not raise any problems
OUTDOOR UNIT
  Do not use the supplied drain nipple for draining water. Drain the water 
from all the drain holes directly.
  To protect the outdoor unit from snow accumulation, install a holding 
frame, and attach a snow protection hood and plate.
*  Do not use a double-stacked design.
Precautions about Installation in Regions
with Snowfall and Cold Temperatures
CAUTION
1.  Install the outdoor unit without anything blocking the air discharging.
2.  When the outdoor unit is installed in a place always exposed to strong 
wind like a coast or on a high storey of a building, secure the normal fan 
operation using a duct or a windshield.
3.  In particularly windy areas, install the unit such as to avoid admission of 
wind.
4.  Installation in the following places may result in trouble.
  Do not install the unit in such places.
    A place full of machine oil
    A saline-place such as the coast
    A place full of sulfi de gas
    A place where high-frequency 
waves are likely to be generated 
as from audio equipment, welders, 
and medical equipment
Strong 
wind
Snow protection plate
Snow protection hood
Snow accumulation line
Holding frame
At least
50 cm
Install at least 50 cm
above the snow
accumulation line.
Anchor
bolts
Front
Installation Place
  A place which provides the spaces around the outdoor unit as shown in 
the diagram
  A place which can bear the weight of the outdoor unit and does not allow 
an increase in noise level and vibration
  A place where the operation noise and discharged air do not disturb your 
neighbors
  A place which is not exposed to a strong wind
  A place free of a leakage of combustible gases
  A place which does not block a passage
  When the outdoor unit is to be installed in an elevated position, be sure to 
secure its feet.
  The allowable length of the connecting pipe.
CAUTION
When the outdoor unit is installed in a place where the drain water might 
cause any problems, Seal the water leakage point tightly using
a silicone adhesive or caulking compound.
     Precautions for adding refrigerant
Use a scale having a precision with at least 10 g per index line when adding 
the refrigerant.
Do not use a bathroom scale or similar instrument.
Do not form the
drain hose into
a wavy shape.
Do not rise the
drain hose.
50 mm
or more
Do not put the
drain hose end
into water.
Do not put the
drain hose end
in the drainage ditch.
Drainage
1.  Run the drain hose sloped downwards.
NOTE
  The hole should be made at ah slight downward slant on the outdoor side.
Shield pipe
Inside the room
Drain hose
Extension drain hose
2.  Put water in the drain pan and make sure that the water is drained out of 
doors.
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.
CAUTION
This air conditioner has the structure designed 
to drain water collected from dew, which forms 
on the back of the indoor unit, to the drain pan. 
Therefore, do not store the power cord and other 
parts at a height above the drain guide.
Drain
guide
Space for pipes
Wall
3.  When connecting extension drain hose, insulate the connecting part of 
extension drain hose with shield pipe.
6