Evacuating
After the piping has been connected to the indoor unit, you can perform the 
air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using a 
vacuum pump. Do not use the refrigerant in the outdoor unit.
For details, see the manual of the vacuum pump.
Be sure to use a vacuum pump with counter-À ow prevention function so that 
inside oil of the pump does not À ow backward into pipes of the air conditioner 
when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use R32, 
refrigeration cycle trouble may result.)
1.  Connect the charge hose from the manifold valve to the service port of 
the packed valve at gas side.
2.  Connect the charge hose to the port of the vacuum pump.
3.  Open fully the low pressure side handle of the gauge manifold valve.
4.  Operate the vacuum pump to start evacuating. Perform evacuating for 
about 15 minutes if the piping length is 20 meters. (15 minutes for
20 meters) (assuming a pump capacity of 27 liters per minute)
Then con¿ rm that the compound pressure gauge reading is –101 kPa
(–76 cmHg).
5.  Close the low pressure side valve handle of the gauge manifold valve.
6.  Open fully the valve stem of the packed valves (both gas and liquid 
sides).
7.  Remove the charging hose from the service port.
8.  Securely tighten the caps on the packed valves.
Packed valve at liquid side
Service port (Valve core (Setting pin))
Packed valve at gas side
Vacuum
pump
Vacuum pump adapter for
counter-À ow prevention
Charge hose
Handle High
(Keep full closed)
Manifold valve
Pressure gauge
Compound pressure gauge
Handle Low
Charge hose 
Connecting pipe
–101 kPa
(–76 cmHg)
CAUTION
•  KEEP IMPORTANT 7 POINTS FOR PIPING WORK.
  (1)  Take away dust and moisture (inside of the connecting pipes).
  (2)  Tighten the connections (between pipes and unit).
  (3)  Evacuate the air in the connecting pipes using a VACUUM PUMP.
  (4)  Check gas leak (connected points).
  (5)  Be sure to fully open the packed valves before operation.
  (6)  Reusable mechanical connectors and À ared joints are not allowed 
indoors. When mechanical connectors are reused indoors, sealing 
parts shall be renewed. When À ared joints are reused indoors, the 
À are part shall be refabricated.
  (7)  Don’t operate air conditioner in case no refrigerant in the system.
     Using a vacuum pump
     Packed valve handling precautions
•  Open the valve stem all the way out, but do not try to open it beyond the 
stopper.
Pipe size of Packed Valve Size of Hexagon wrench
12.70 mm and smallers A = 4 mm
15.88 mm A = 5 mm
•  Securely tighten the valve cap with torque in the following table:
Cap Cap Size (H) Torque
Valve Rod Cap
H17 - H19
14~18 N·m
(1.4 to 1.8 kgf·m)
H22 - H30
33~42 N·m
(3.3 to 4.2 kgf·m)
Service Port Cap
H14
8~12 N·m
(0.8 to 1.2 kgf·m)
H17
14~18 N·m
(1.4 to 1.8 kgf·m)
 
A
H
Hexagon wrench
is required.
Service Port Cap
Valve Rod Cap
Pump down process
1.  Turn off the Air Conditioner system.
2.  Connect the charge hose from the manifold valve to the service port 
of the packed valve at gas side.
3.  Turn on the Air Conditioner system in cooling operation more than 
10 minutes.
4.  Check the operating pressure of the system should be normal value. 
(Ref. with product specifi cation)
5.  Release the valve rod cap of both service valves.
6.  Use the Hexagon wrench to turning the valve rod of Liquid side fully 
close. (*Make sure no entering air into the system)
7.  Continue operate Air Conditioner system until the gauge of manifold 
dropped into the range of 0.5 - 0 kgf/cm
2
.
8.  Use the Hexagon wrench to turning the valve rod of Gas side fully close.
And turn off the Air Conditioner system immediately thereafter.
9.  Remove the gauge manifold from the service port of the packed valve.
10. Securely tighten the valve rod cap to the both service valves.
CAUTION
Should be check the compressor operating condition while pumping
down process. It must not any abnormal sound, more vibration.
It is abnormal condition appears and must turn off the Air Conditioner 
immediately.
8