– 24 –
Item Operation flow and applicable data, etc. Description
1. Basic
operation
1-5. AUTO operation
Ta: Room temp.
Ts: Setup temp.
To: Outside temp.
k = deg
1) The judgment of selecting COOL/HEAT is carried out as shown
below. When +1.5 exceeds against Tsh 10 minutes and after
thermo. -OFF, heating operation (Thermo. OFF) exchanges to
cooling operation. Description in the parentheses shows an example
of cooling ON/OFF.
When –1.5 lowers against Tsc 10 minutes and after thermo. OFF,
cooling operation (Thermo. OFF) exchanges to heating operation.
2) For the automatic capacity control after judgment of cooling/heating,
see Item 4.
3) For temperature correction of room temp. control in automatic
heating, see Item 3.
Tsc: Setup temp. in cooling
operation
Tsh: Setup temp. in heating
operation + temp.
correction of room
temp. control
1-6. DRY operation
DRY operation is aimed to dehumidification.
In order to prevent lowering of the room temperature,
Indoor fan speed is fixed to cooling L tap.
Cooling capacity is restricted to low. When the room temperature is
lower than the setup temperature, the compressor is turned off.
Remote controller
command
Control outline
AUTO
COOL/HEAT operation mode is
automatically selected by Ta, Ts
and To for operation.
The operation is performed as
shown in the following figure
according to Ta value at the first
time only. (In the range of Ts + α
–1 < Ta < Ts + α + 1, Cooling
thermo. OFF (Fan)/Setup air
volume operation continues.)
α is corrected according to the outside temperature.
Cooling
operation
Cooling thermo. OFF (Fan only)
Setup air volume
+1.0
Ts +
α
Ta
(°C)
-1.0
Heating
operation
Outside temp.
Correction value (
α)
No To 0K
To 24°C –1K
24 > To 18°C 0K
To < 18°C +1K
To error 0K
Cooling
Cooling OFF
or
Ta
(°C)
-1.5
Heating
(Cooling ON)
+1.5
Tsc
Tsh