8-3. Temporary Operation
• Temporary Auto operation, existence of Auto
Restart, and Temporary Cooling operation can be
set by the TEMPORARY button of the indoor
controller.
8-3-1. Temporary Auto Operation
• When the TEMPORARY button is pushed, the
Auto operation with set temperature fixed at 24°C
starts. Controlling is same as that of Auto opera-
tion by the remote control.
• When the TEMPORARY button is pushed again,
the operation stops.
• During Temporary Auto operation, operation by
the remote control is accepted.
• Using the Auto Restart function, the Temporary
Auto operation starts when power failure is reset.
8-3-2. Temporary Cooling Operation
• When the TEMPORARY operation button keeps
pushed for 10 seconds, Cooling operation of
which compressor motor speed and the indoor
fan speed are fixed starts.
Compressor motor speed : 28 rps
Indoor fan speed : Low
• When the TEMPORARY operation button is
pushed again, the operation stops.
• Auto Restart function is unavailable.
TEMPORARY button Control
OFF
→→
→→
→ ON Temporary Auto operation start
After pushing button
Auto Restart control select
for 3 seconds
After pushing button Temporary Cooling
for 10 seconds operation start
TEMPORARY button
0
3S
Fig. 8-3-1
Table 8-3-1