62
Wiring port
D11 D12 D13 D14 D15
LED (Red)
10-6. Trouble Diagnosis by Outdoor LED
For the outdoor unit, the self-diagnosis is possible by
five LEDs (Red).
LEDs (Red) (D11 to D15) are provided on the
sub-control board under surface of the inverter,
and as shown below, they are checked from the
wiring port when removing the wiring cover.
1. If a trouble occurs, LED (Red) goes on accord-
ing to the trouble as described in the table below.
2. When two or more troubles occur, LEDs go on
cyclically.
3. Usually, LEDs (Red) go off.
Fig. 11-6-1
¤
: LED ON,
l
: LED OFF P.M.V. : Pulse modulating valve
LED display
D11 D12 D13 D14 D15
lllll
¤
llll
l
¤
lll
¤¤
lll
ll
¤
ll
l
¤¤
ll
¤¤¤
ll
lll
¤
l
¤
l
¤
ll
*
2
¤¤¤¤
l
*
2
¤
lll
¤
*
2
¤¤
ll
¤
*
1
l
¤¤
l
¤
*1
¤¤¤l ¤
lll
¤¤
¤¤
l
¤¤
¤
ll
¤
l
l
¤
l
¤
l
¤¤
l
¤
l
Indoor
check
code
None
07
14
16
17
19
1A
1B
1C
––
––
––
––
––
1C
1D
1E
1F
Description
During normal operation
Compressor thermo. operation, instantaneous power failure,
gas leak
IGBT short circuit, compressor motor rear short
Position-detect circuit error
Current-detect circuit error
Discharge temp. sensor (TD) error
Outdoor fan error
Outside temp. sensor (TO) error
Compressor system error
A room gas side temp. sensor (TGa) error
B room gas side temp. sensor (TGb) error
C room gas side temp. sensor (TGc) error
Gas leakage, P.M.V. sensor error
Indoor heat exchanger sensor (TC) disconnection, P.M.V.
sensor error
Indoor/outdoor miswiring, gas leakage, TC sensor
disconnection, P.M.V. sensor error
Communication error between MCU
Compressor lock
Discharge temp. error, gas leakage
Compressor break down
*
1 Back-up operation is performed without block display of the indoor unit.
*
2 Operated normally when the air conditioners in other rooms are driven.