Item
Test method
Decision Test
circuit
(single
phase)
Qperat-
Slowly reduce the
75%
rtlO%
of the rated
Figure 16
ing
current and measure
current
(IN)
point the current value at
JB
which the relay trips.
Clperat-
1)
Apply the rated
Less than 4 s. Figure 16
ing
current
(IN).
time
2) Quickly change
current in one phase
to 0 and measure the
time it takes for
the relay to trip.
Unbal-
1)
Apply the rated
ante
current
(IN).
factor
I
II
-
IAVE
I x
loo%
IN
Figure 16
2)
Change current in
The calculated value must be
one phase and
within
*5%
of the setting
measure the current value.
at which the relay
trips.
Example: When the setting
value is 30%. the
calculated value
must be in the
range of 25 to 35%.
--
--
1
I:
Measured current value.
-
102
-
www . ElectricalPartManuals . com