T1000 Series UPS 1000-3000VA Installation and Operation Manual – 94086-001 39
16 TECHNICAL SPECIFICATIONS
16.1 POWER RANGE 1000VA - 3000VA (120V MODEL)
True Online, Double-Conversion
90-144V @ Full Load
Minimum: 60V at 25%, 70V at 50%, 80V at 75% Load
100/110/115V (selectable from LCD panel)
< 5% THD at full non-linear load,
< 2.5% THD at full linear load
± 0.25 Hz (battery or free running mode)
106-120% 30sec.; 121-150% 10sec.
Internal Bypass (Automatic and Manual)
WARNING:
When power is supplied by external batteries, output towards load should be less than
90% of overall power generation.