T1000 Series UPS 1000-3000VA Installation and Operation Manual 94086-001 40
16.2 POWER RANGE 1000VA - 3000VA (230V MODEL)
GENERAL
1000VA
1500VA
2000VA
3000VA
Rated power
1000VA
1500VA
2000VA
3000VA
Capacity (W)
900W
1350W
1800W
2700W
Topology
True Online, Double-Conversion
Phase
Single Phase
INPUT
Nominal Input Voltage
230V
Input Voltage Range
180-276V @ Full Load
Minimum: 120V @ 25%, 140V @ 50%, 160V @ 75% Load
Input Frequency
45-65 Hz (auto-sensing)
Input Power factor
0.97
Rated Input Current
4.7A
7.0A
9.4A
14.1A
OUTPUT
Output Power Factor
0.9
Nominal Output Voltage
230V
Other Output Voltage:
208/220/240V (selectable from LCD panel)
Voltage regulation:
± 2%
Voltage distortion
< 5% THD at full non-linear load,
< 2.5% THD at full linear load
Rated Current @ 230 VAC
4.3A
6.5A
8.7A
13A
Output Frequency
50/60 Hz +/- 5%
Frequency regulation
± 0.25 Hz (battery or free running mode)
Wave Form Type
Sine Wave
Overload capacity
106-120% 30 sec, 121-150% 10 sec
Bypass
Internal Bypass (Automatic and Manual)
Crest Factor
3:1
Efficiency
> 86%
WARNING:
When power is supplied by external batteries, output towards load should be less than
90% of overall power generation.