36 TC-net 100 Installation and Wiring Manual
Chapter 6 Grounding
6
Caution
Check the wiring routes and make the grounding wires as short as possible.
Use grounding wires 2 mm
2
or larger and 1 m long or less.
Do not join grounding wires nor use a chain of wires between grounding busbars (lead-in ter-
minals).
If a metal pipe, for example, is used to separate the Ethernet trunk cables from other cables,
be sure to ground the metal pipe by Class D grounding. This grounding must be indepen-
dent of the grounding of transmission lines (coaxial segments and transmission parts).
Ground the transmission parts as follows:
Cabinet of Class D grounding or higher exclusive to the Integrated Controller: Cabinet can
be grounded.
Mixed presence of cabinet grounding and other grounding: Use exclusive Class D ground-
ing.
To ground twisted-pair cables, provide the cabinet, where a hub is installed, a means of
grounding and ground the hub at one point. To ground the cable connecting one hub to
another, ground either of the hubs at one point.
If power noise is likely to be generated, use a noise filter in the power line of the transmission
parts, and ground it to the grounding terminal exclusive to the Integrated Controller.
If errors or defects have developed, contact your nearest TOSHIBA service office.