40 TC-net 100 Installation and Wiring Manual
Chapter 6 Grounding
6
6.2 Grounding Transmission Parts
Ground the transmission parts (optical shared hub units, electrical shared hub units) by
class D grounding as follows: The Class D grounding exclusive to transmission parts is
recommended.
6.2.1 Grounding hubs
In grounding the hubs, either share the grounding pole exclusive to the Integrated
Controller, or prepare a grounding pole exclusive to the transmission parts.
Grounding exclusive to the Integrated Controller
Ground the hubs by fastening the cabinet mounting plate for the hubs directly to the
cabinet.
Mixed presence of the grounding of the Integrated Controller and that of other devices
Either insulate the cabinet mounting plate for the hubs from the cabinet, or insulate the
hubs from the cabinet mounting plate.
Connect the grounding pole of the power cable to the grounding pole of the
transmission line, not to that of other devices.
6.2.2 Grounding connectors, etc.
Insulate the connectors, etc. to keep them free of contact with other metal parts.

Table of Contents

Other manuals for Toshiba TC-net 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TC-net 100 and is the answer not in the manual?

Toshiba TC-net 100 Specifications

General IconGeneral
BrandToshiba
ModelTC-net 100
CategoryNetwork Hardware
LanguageEnglish

Related product manuals