Fn #  Group  Function Description  Adjustment / Display Range 
Setting 
Increments 
Factory 
Setting 
Setting
F040 
Current and Ground Fault Protection 
Current Imbalance Trip  
0 = Disabled, or  
5 - 30% imbalance 
1% 0 Disabled  
F041  Current Imbalance Trip Delay  1 - 20 seconds  1 second  2 seconds   
F042  Over Current Trip 
0 = Disabled, or  
100 - 300% of motor FLA 
1% 0 Disabled  
F043  Over Current Trip Delay  1 - 20 seconds  1 second  1 second   
F044  Under Current Trip 
0 = Disabled, or  
10 - 90% of motor FLA 
1% 0 Disabled  
F045  Under Current Trip Delay  1 - 60 seconds  1 second  2 seconds   
F046 Ground Fault Trip 
0 = Disabled, or 
5 - 90% of CT ratio from Fn 74 
1% 0 Disabled  
F047  Ground Fault Trip Delay  1 - 60 seconds  1 second  2 seconds   
F048 
Lockouts, Reset and Internal Protection 
Coast Down (Back Spin) 
Lockout Timer 
0 = Disabled, or 1 - 60 minutes  1 minute  0 Disabled   
F049  Maximum Starts per Hour  0 = Disabled, or 1 – 10 starts  1  0 Disabled   
F050  Minimum Time Between Starts  0 = Disabled, or 1 - 60 minutes  1 minute  0 Disabled   
F051  Internal Protection Settings  1 – 255  1  126   
F052 
Auto Reset  
on Selected Faults 
Fault Preferences 1 – 12 
See Fault Reset Selection Table 
1 
4:  
Phase Loss 
only 
 
F053  Auto Reset Attempts  0 = Disabled, or 1-10 attempts  1  1   
F054 
Restart Delay Time Value 
Readout (for F028) 
0-999 Seconds  1 0  
F055 
Coast Down Timer Value 
for F048 
1-3600 Seconds  1 0  
F056 
Starts Per Hour Timer Value 
for F049 
1-3600 Seconds  1 0  
F057 
Starts Per Hour 
For F049 
1-10 Starts  1 0  
F058 
Time Value Between Starts 
for F050 
1-3600 Seconds  1 0  
F059 
Thermal Capacity to Start 
for F005 
0-100 % Thermal Capacity  1  0   
F060 
Output Relays 
Aux Relay 1 setting  
Operation # 1 – 27: see 
”Aux. Relay Settings Chart” 
1 1  
F061  Aux Relay 2 setting 
Operation # 1 – 27: see 
”Aux. Relay Settings Chart” 
1 2  
F062  Aux Relay 3 setting 
Operation # 1 – 27: see 
”Aux. Relay Settings Chart” 
1 16  
F063 
Aux. Relay Delay Timer 
(for Operations 22-26) 
0 (Disabled), or 1-999 seconds  1 second 
0  
No Delay 
 
F064  Reserved for factory use         