If the battery voltage is higher than the maximum threshold of 2, 60 V/cell, the charger doesn’t
start, and the display will show the (flashing) error message “Voltage High”:
If the voltage of the battery is between the minimum and maximum thresholds, the charger will
wait for 3 seconds before to start charging, while the display will show the programmed
Opportunity Pause.
If, during the charge, the voltage of the battery exceeds the maximum threshold of 2, 80 V/cell,
the charger shuts down automatically, and the error message “Voltage High” will appear on
the display.
CHARGE OPERATION
When the charge is started, the digital display will start showing the
following parameters:
• Voltage per cell of the battery (U) (Volt);
• Charge current; (A) (Ampere);
• Capacity charged; (C) (Ah);
• Time of charge. (h) (Hours);
During all the charge cycle these parameters are displayed in
sequence, as indicated in the picture.
The letter (U-A-C-h) indicates which parameter being is displayed.
To display the time, the charger uses this format:
(HOURS) . (MINUTE DECADES) h
Examples:
Time of charge 3h 30minutes: Displayed 3.3h
Time of charge 7h 50minutes: Displayed 7.5h
When the battery reaches the gassing voltage, the charge stops and waits for the end of the
Opportunity Pause. When the Opportunity Pause finishes or it has been set equal to 0 hour the
second (final) phase of charger begins.
The second phase will be ON for one half of the time needed to reach the gassing voltage
(time of first phase), with a minimum total time of 30 minutes.
Examples: