EasyManua.ls Logo

Totem 10 - Operator Panel Settings; Starting and Working Principle

Totem 10
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Settings
The “Settings sreenshots
C.
Start
TOTEM
units work based on the thermal
automatically
load is
present
TOTEM
unit.
In addition to fulfillin
by the User by operating
Once start is
under the following
The t
emperature value can be set in
in the range from
In addition to the start temperature
set. When the temperature of water
unit
automatically
The unit is
also
the pump start command
commanded to stop with a delay that can be set by the user. The delay is
let water circulate
User’s Guide | TOTEM 10
The Settings” sreenshots
allows to set some of the unit’s operating parameters
Start temperature
Stop temperature
External pump stop delay
Start
ing and Working Principle
units work based on the “thermal
priority” principle,
that
automatically
switch to simultaneous
delivery of heat and electricity
present
that allows to recover heat from the internal
recovery
unit.
In addition to fulfillin
g the aforementioned condition
, the unit’s Start must
by the User by operating
the “ON” button that is found on
the Operator panel.
Once start is
enabled, the TOTEM starts functioning fol
lowing a demand
under the following
conditions:
Activation of the User’s Water system circulator
pum
the unit’s on-board flow switch;
Water temperature below the value set by the User.
emperature value can be set in
the “Setting
s” screenshot on the Operator Panel
in the range from
30 to 70°C.
In addition to the start temperature
value
, the stop temperature
set. When the temperature of water
from the supply line
exceeds the set value, the
automatically
stops, going into stand-by mode.
also
fitted with an external
pump control outlet. When the st
the pump start command
is also enabled. When the unit
stops,
commanded to stop with a delay that can be set by the user. The delay is
let water circulate
within the unit after it is switched off thus
allowing
Users Guide | TOTEM 10
- TOTEM 20
23 of 30
allows to set some of the units operating parameters
that
is to say, they
delivery of heat and electricity
whenever a heat
recovery
system of the
, the units Start must
be enabled
the Operator panel.
lowing a demand
for heat
pum
p, as detected by
Water temperature below the value set by the User.
s screenshot on the Operator Panel
, the stop temperature
value will also be
exceeds the set value, the
pump control outlet. When the st
art is enabled
stops,
the pump is also
commanded to stop with a delay that can be set by the user. The delay is
needed to
allowing
it to cool down.