Requirements for Cabling Indoors
 
When cabling indoors, keep a certain distance away from the devices that may cause 
high-frequency  interferences,  such  as  down-conductor  cable,  powerline,  power 
transformer and electromotor.
The main cable  should be paved in the  metal raceway of the access shaft. When 
 
cabling, keep the loop area formed by the cable itself as small as possible.
Requirements  for  the  distance  between  Ethernet  cable and  other  pipelines are 
 
shown in the table.
Other Pipelines
Ethernet Cable
Min Parallel Net Length L 
(mm)
Min Parallel-overlapping 
Net Height H (mm)
Down-conductor 1000 300
PE 50 20
Service pipe 150 20
Compressed air pipe 150 20
Thermal pipe (not wrapped) 500 500
Thermal pipe (wrapped) 300 300
Gas pipe 300 20
The two diagrams below demonstrate parallel net length and parallel-overlapping net 
height.
Note: The  above minimum  net length/height  is required when metal raceway is not 
used. If any requirements cannot be met, you can add a steel tube or metal raceway 
for shielding.
Requirements  for the  distance  between  Ethernet  cable  and  high-power  electric 
 
devices are in following tables.
Cable Pave Way
Min Parallel 
Length (mm)
<2kVA 
powerline
Parallel cabling 130
One is in the grounded metal raceway or metal pipe 70
The both are in the grounded metal raceway or metal 
pipe
10
Lightning Protection