2~5kVA 
powerline
Parallel cabling 300
One is in the grounded metal raceway or metal pipe 150
The both are in the grounded metal raceway or metal 
pipe
80
>5kVA 
powerline
Parallel cabling 600
One is in the grounded metal raceway or metal pipe 300
The both are in the grounded metal raceway or metal 
pipe
150
Device Min Distance (m)
Switch case 1.00
Transformer room 2.00
Elevator tower 2.00
Air-conditioner room 2.00
Connecting  the device to  ground is  to quickly  release  the lightning over-voltage and 
over-current of the device, which is also a necessary measure to protect the body from 
electric shock. 
In  different  environments,  the  device may  be  grounded differently.  The  following 
will instruct  you to connect  the device to the ground in two  ways, connecting to the 
grounding bar  or  connecting  to  the ground via the  power cord.  Please  connect the 
device to ground in the optimum way according to your specific operation environment. 
Connecting to the Grounding Bar
 
If the device  is installed in the Equipment Room, where  a grounding bar is available, 
you are recommended  to connect  the  device  to the  grounding bar  as shown in the 
following figure.