26 BAS-SVX44C-EN
Configuration Option Setup
0180
Changeover 1 0= Manual 1= Auto
Only for systems with both heat and cool stages. (Refer to
0181
Deadband 3 •2= 2°F (1°C)
•3= 3°F (1.5°C)
•4= 4°F (2.0°C)
•5= 5°F (2.5°C)
•6= 6°F (3.0°C)
•7= 7°F (3.5°C)
•8= 8°F (4.0°C)
•9= 9°F (4.5°C)
Only applies to auto or manual changeover systems. (Refer to
Option 0180.)
0182
Minimum Compressor Off
Time
5 • 0= 0 minutes
• 1= 1 minute
• 2= 2 minutes
• 3= 3 minutes
• 4= 4 minutes
• 5= 5 minutes
Only for systems with cool stage or heat pump. (Refer to
Option 0130.) This setting will extend the compressor OFF
time beyond any other delays incorporated in the Heat/Cool
software algorithm.
0190
Power Supply Frequency 0 0= 60 Hz 1= 50 Hz
Power supply input is 24 Vac nominal at either 60 Hz or 50 Hz.
0200
Dehumidify Sensor
Selection
1 • 0= Humidity display and
function is disabled
• 1= Internal humidity sensor
enabled
2= External humidity sensor enabled
For external humidity control, a 4–20 mA humidity sensor
must be connected to the Hp and Hs terminals to avoid error
code E1.
0205
Dehumidification Control 0 0= Active Control 1= Passive Control
Active control toggles Dh output terminal ON and OFF as
specified by the dehumidify algorithm and is used with a
device having its own dehumidification equipment. Passive
control runs cool mode for up to 1 extra minute whenever there
is a call for cool and dehumidification.
0206
Internal Humidity Offset
Adjustment
0 -9% to 9% in 1% increments
Allows adjustment of the internal relative humidity reading to
account for accuracy, tolerance, and potential drift. FW should
use the adjusted value for display and humidity control.
0207
External Humidity Offset
Adjustment
0 -9% to 9% in 1% increments
Allows adjustment of the external relative humidity reading to
account for accuracy, tolerance, and potential drift. FW should
use the adjusted value for display and humidity control.
0210
Temperature Sensor
Selection
0 • 0= Internal sensor only (10k)
• 1= Internal sensor for H/C
control (outdoor for display
only) [10k]
• 2= internal sensor for H/C
control (outdoor for Compr/Aux
lockout control([10k]
• 3= Remote indoor sensor for H/
C control (10k)
• 4= Use average temperature =
(local+S1/S2)/2 for H/C
control.
Setting 2 applies only to HP systems and is disabled on all
conventional systems.
For setting 1, 2, or 4; if either temperature sensor is out of
range, then the E0 error code will display.
0220
Heat Pump Compressor
Lockout Point
0 •0= None
• 15= 15°F (–9.5°C)
• 20= 20°F (–6.5°C)
• 25= 25°F (–4.0°C)
• 30= 30°F (–1.0°C)
• 35= 35°F (1.5°C)
• 40= 40°F (4.5°C)
• 45= 45°F (7.0°C)
Only for heat pump systems with more heat stages than cool
stages and remote outdoor control sensor. (Refer to Option
0130 and Option 0210.)
Note: A 5°F (2.5°C) deadband between heat pump and
auxiliary lockout will be enforced.
0221
Heat Pump Auxiliary Lockout
Point
0 •0= None
• 40= 40°F (4.5°C)
• 45= 45°F (7.0°C)
• 50= 50°F (10.0°C)
• 55= 55°F (13.0°C)
• 60= 60°F (15.5°C)
Only for heat pump systems with more heat stages than cool
stages and remote outdoor control sensor. (Refer to Option
0130 and Option 0210.)
Note: A 5°F (2.5°C) deadband between heat pump and
compressor lockout will be enforced.
0230
Temporary Override
Duration Limit
3 •0= zero hours
• 1= one hour
• 2= two hours
• 3= three hours
• 4= four hours
Used for temporary override (TOV) starting duration time.
Setting of zero does not disable TOV.
0231
Starting Default Number of
Periods
2 2= two periods 4= four periods
Provides starting default number of periods for all days of the
week.
Table 7. Installer configuration setup menu (continued)
Opt.
No.
Name Def Values/Descriptions Notes