When paired with a communicating outdoor unit, the
Air Handler control board will auto-discover the outdoor
unit size. Default settings are 400 cfm/ton and 1.5
minute at 100% cfm off delay. For other airflow set-
tings, access the User Interface Menu (See Figure 18)
to select options or use the options in the communicat-
ing Comfort Control. The full menu is listed in Figure
19.
When Air Handler is to be used in 24V mode, ac-
tess the User Interface to change the comfort con-
trol mode to 24V, match the airflow for the out-
door unit size (tons), adjust the cooling airflow
(cfrniton), set the Fan on!off-delay options, and
adjust the heating airflow per the Nameplate
specifications on the air handler front panel. The
User Interface appears as shown in Figure 18. The full
menu is listed in Figure 20.
If the airflow needs to be increased or decreased, see
the Blower Performance Table in the Service Facts. In-
formation on changing the speed of the blower motor
for your specific outdoor model size is in the Blower
Performance Table.
Be sure to set the airflow for the correct tonnage.
Refer to the User Interface for correct setting.
If the optional humidistat is used, remove R-BK jumper
from the low voltage terminal board (not shown) and in-
stall the humidistat between R and BK. (Jumper R to O
for cooling-only/non-heat pump systems with a humidis-
tat.)
K. UNIT TEST MODE
Unit Test Mode (Air Handler)
The system must be idle or thermostat switched to
"OFF" before the Unit Test will run the air handler.
The unit will work the same way in either
Communicating or 24VAC modes.
To access the Unit Test Mode scroll down through
the User Interface Information Menu until you see
Installer's Guide
the Unit Test option. Press ENTER. When
prompted select YES and press ENTER. When the
User Interface displays ARE YOU SURE? select YES
and press ENTER to begin the Unit Test.
NOTE: While in Test Mode all thermostat requests
will be ignored but if any button on the User
Interface is pressed, the Unit Test will exit. The Unit
Test will exit if a fault is detected during the test
sequence.
The Unit Test will perform the following steps
without delays.
1. Start blower at 50% airflow and Energize EAC
relay.
2. After 10 seconds, go to 100% airflow for 10 seconds.
(User Interface displays UNIT TEST - BLWR)
3. Energize Y1 relay for 15 seconds with 100% airflow.
(User Interface displays UNIT TEST - COOL)
4. De-energize Y1 relay and go to Electric Heat
airflow.
(User Interface displays UNIT TEST - HEAT)
5. Energize blower interlock and stage 1 heat relay.
6. Energize humidifier relay.
7. After 1 second energize stage 2 heat relay.
8. After 1 more second energize stage 3 heat relay.
9. After 5 seconds de-energize blower interlock, stage
1, 2 & 3 heat, humidifier and EAC relays.
(User Interface displays UNIT TEST - EXIT)
Displayed for three seconds
NOTE: Airflow is default or programmed selections.
Figure 18
Viewing Window
USERINTERFACE
Push left & right to scroll
through menu options
Push up & down
to scroll through
setup menu
/
/
Push ENTER to make selection
User Interface pictured above adjusts variable speed airflow options.
18-GE11 D1-4 11