Installer's Guide
FIGURE 19- USER INTERFACE MENU - COMMUNICATING MODE
Standby Screen
MODEL NUMBER
SERIAL NUMBER
Setup Menu
CMFRT CNT MODE
1 "_COMM [COMM] 24VACl
1
[ COOLING CFM
i CFM PER TON
i HEAT CFM
Setup Options
[ ] denotes the current setting
m=minutes
.COOLING CFM (_
CFM PER TON
400 [400] 430 450 290 310 330 350 370
HEATCFM
t
* unit specific
Model COOLING CFM options
31 3T [3T] 1½T 2T 2½T
37 3T [3T] 3½ 2T 2½T
40 3½T [3½T] 2T 2½T 3T
49 4T [4T] 5T 3T 3½T
65 5T [5T] 3T 3½T 4T
**unitspecific
Model HEAT CFM o_ions
31 1130 [1130] 1350 700 1000
37 1100 [1100] 1450 600 900
40 1100 [1100] 1400 600 900
49 1400 [1400] 1700 800 1100
65 1500 [1500] 1800 900 1200
i FACTORY DEFLTS ].._ FACTORY DEFLTS
NO [NO] YES
i EXIT J_ F-XIT
NO [NO] YES
Information Menu
IMODEL NUMBER
ISERIAL NUMBER
ISYSTEM STATUS
IREQUESTED CFM
ILAST 4 FAULTS
I INDOOR ALERTS
IUNIT TEST
ITEMP SENSOR
IMOTOR RPM
IRESET LST FAULT
ICLEARLITEPORT
IRESET HEAT SENSE
IPART LIST
IPM SERIAL NUM
IEXIT
Information Options
• MODEL NUMBER
2/4TEE3C_*A1000A
• _UMBER
• S***YSTEM STATUS
t
• REQUESTED CFM
0 CFM
• LAST4 FAULTS
==NO ALERTS==
t
• INDOOR ALERTS
==NO ALERTS==
t
• UNIT TEST
NO [NO] YES
• TEMP SENSOR
SNSR1 [SNSR1] SNSR2 DLT2-1
t
• MOTOR RPM
0 RPM
t
• RESET LST FAULT
NO [NO] YES
t
• CLEAR LITEPORT
NO [NO] YES
• RESET HT SENSE X
NO [NO] YES
t
• PART LIST
D SPLAY CNT ##f##f
• _RIAL NUM
• EXIT
NO [NO] YES
*** unit specific
[Can be 31, 37, 40, 49 or 65 1
*_ SYSTEM STATUS Options
OFF
ON FAN
ON CLG# (#: Highest active cooling stage)
ON HP# (#: Highest active HP stage)
ON HT rTrTr7
ON HP+HT #+ 171717 (#: Highest active HP stage)
An open box, rq designatesa contactor
sensed, but not energized. A closed box,
e, designates a contactorthat is energized,
present, or not. A hyphen, -, designates s
contactornot sensed and not energized.
Notes:
(_ Shown only when Outdoor Communicating Unit is not detected.
(_)X indicates actual number of heat banks detected under reset menu.
[PRINTED FROM D802236P01 REV 2 I