14 MS-SVN052E-EN
Unit Installation
Figure 9. Piping Length Diagram #1
Always use the shortest length possible with a minimum amount of curves.
Note: Excessively long refrigerant lines produce capacity loss for the equipment.
Vertical Rise
Keep the vertical rise at a minimum. See the following guides for unit installation.
1. DO NOT exceed vertical rise as indicated in Tabl e 3 .
2. It is recommended to use the smallest allowable size for liquid line in order to minimize system
charge. This will maximize compressor reliability.
Tab l e 3 may be used to define dimensions for horizontal runs.