18-GF14D1-1C-EN
29
A4AH6V24A1B30B, A4AH6V30A1B30B
Heater Minimum Heater Airflow CFM
With Heat Pump Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG
BAYHTR1505BRK, BAYHTR1505LUG
660 600
BAYHTR1508BRK, BAYHTR1508LUG
780 600
BAYHTR1510BRK, BAYHTR1510LUG
780 600
BAYHTR1517BRK
1050 850
BAYHTR3510LUG
780 600
BAYHTR3517LUG
900 850
A4AH6V36A1C30B, A4AH6V42A1C30B
Heater Minimum Heater Airflow CFM
With Heat Pump Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG
BAYHTR1505BRK, BAYHTR1505LUG
875 675
BAYHTR1508BRK, BAYHTR1508LUG
950 820
BAYHTR1510BRK, BAYHTR1510LUG
1000 820
BAYHTR1517BRK
1000 820
BAYHTR3510LUG
875 820
BAYHTR3517LUG
1000 950
BAYHTR1523BRK
1300 1140
A4AH6V48A1C30B, A4AH6V60B1C30A
Heater Minimum Heater Airflow CFM
With Heat Pump Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG
BAYHTR1505BRK, BAYHTR1505LUG
1200 975
BAYHTR1508BRK, BAYHTR1508LUG
1350 975
BAYHTR1510BRK, BAYHTR1510LUG
1350 975
BAYHTR1517BRK
1365 975
BAYHTR3510LUG
1300 975
BAYHTR3517LUG
1365 1120
BAYHTR1523BRK
1365 1300
BAYHTR1525BRK
1810 1505
A4AH6V24A1B30B Airflow Performance with Auxiliary Heat
Airflow Settings
Dip Switch Settings
Nominal Airflow
See following tables for heater application:
- Pressure Drop for Electrical Heaters
- Minimum Heating Airflow Matrix (on unit nameplates)
Switch 7 Switch 8
Low ON ON 601
Med-Lo OFF ON 661
Med-Hi ON OFF 781
High
OFF OFF 973
MMiinniimmuumm AAiirrffllooww CCFFMM