CG-SVX06F-GB
Original instructions
Indoor liquid chiller with integrated hydraulic module
Water-cooled model CGWN and Condenserless model CCUN :
205 - 206 - 207 - 208 - 209 - 210 - 211 - 212 - 213 - 214 - 215
R410A
Installation
Operation
Maintenance

Questions and Answers

  • B
    Bradley FranklinAug 16, 2025
    What causes loss of oil in Trane Chiller compressor?
    • D
      Douglas MartinAug 16, 2025
      Loss of oil in your Trane Chiller's compressor can be caused by: * Insufficient oil. Contact the Trane office before ordering oil. * A clogged filter drier. Replace the filter drier. * Liquid flowing back to the compressor. Adjust the superheat and check the bulb fixing of the expansion valve.
  • B
    Brandon King DDSAug 23, 2025
    Why does my Trane AquaStream 2 CGWN compressor stop?
    • A
      Andrew PittmanAug 25, 2025
      The compressor might stop due to the high pressure switch being tripped. This can be caused by several factors: * Discharge pressure being too high. * Voltage being too low. Contact your power supply utility. * Cooling demand being too high or the condensing temperature being too high. Refer to instructions for 'discharge pressure high'. * Insufficient cooling fluid. Repair the leak and add refrigerant. * Water flow to the evaporator being too low. Check the water flow rate and the flow switch contact in the water.
  • X
    xwashingtonAug 29, 2025
    Why Trane Chiller compressor keeps running without stopping?
    • C
      Christopher GoodmanAug 29, 2025
      If your Trane Chiller's compressor runs continuously, it's likely due to: * Excess load on the cooling system. * Excess cooling demand on the system. In both cases, check the thermal insulation and air-tightness of the areas requiring air-conditioning.
  • D
    David RobertsonSep 4, 2025
    What to do if Trane AquaStream 2 CGWN Chiller compressor stops just after starting?
    • K
      Kimberly McclainSep 4, 2025
      If your Trane Chiller's compressor stops shortly after starting, it might be due to a clogged filter drier. Replace the filter drier to resolve this.
  • T
    Teresa WilliamsNov 10, 2025
    What to do if Trane AquaStream 2 CGWN Chiller compressor does not start up?
    • V
      Vickie MooreNov 10, 2025
      If the compressor on your Trane Chiller isn't starting, here's what you can check: * **Motor:** It may be burned out, requiring a compressor replacement. * **Coil/Contacts:** The coil might be burned out or the contacts broken, needing repair or replacement. * **Power:** There may be a power cut or the main power supply could be switched off. Check the fuses and connections. Determine why the system tripped. If operational, switch on the main power supply. * **Fuse:** A blown fuse could be the issue. Check the motor insulation and replace the fuse. * **Voltage:** Low voltage can prevent startup. Contact your power supply utility. * **Regulation Circuit:** An open regulation circuit could be the cause. Locate the regulation device that has tripped and investigate why. Consult t...