EasyManua.ls Logo

Trane AquaStream 2 CGWN Series - Control and Unit Operation; Weekly Start up; Weekend Shutdown; Seasonal Shutdown

Trane AquaStream 2 CGWN Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CG-SVX06F-GB38
Operation
Control and unit operation
The control is through the
TRACER CH530 control module.
Check the chilled water pump(s)
operate(s)
Start up the unit following
procedure described in the
CGWN-CCUN User Manual. The
unit will operate correctly when
there is sufficient water flow.
The compressors will start up
if the evaporator water leaving
temperature is above the control
module setpoint.
Weekly start up
Check the chilled water pump(s)
operates
Start up the unit following
procedure described in the User
Guide.
Weekend shutdown
If the unit needs to be shut down
for a short period of time, stop the
unit following procedure described
in the CGWN-CCUN User Manual
(See “Clock” menu)
If the unit is shut down for a
longer period, see under “Seasonal
shutdown”, below.
Ensure that all safety precautions
are taken to prevent frost
damages during negative ambient
temperature.
Do not put the general disconnect
switches to off, except if the unit
is drained.
Trane does not recommend draining
the unit, due to the fact that it
increases tube corrosion.
Seasonal shutdown
Check water flows and interlocks.
Check glycol concentration in
the chilled water circuit if glycol
presence is required
Carry out leak test.
Carry out oil analysis
Record operating pressures,
temperatures, amperages and
voltage.
Check operation of machines/
compare conditions of operation
against original commissioning
data.
Stop the unit following procedure
described in the CGWN-CCUN
User Manual.
Ensure that all safety precautions
are taken to prevent frost
damages during negative ambient
temperature.
Fill out the visit log sheet and
review with the operator
Do not put the general disconnect
switch to off, except if the unit is
drained.
Trane does not recommend draining
the unit, due to the fact that it
increases tube corrosion.

Related product manuals