Operation
Seasonal start-up
Check water flows and interlocks.
Check Ethylene glycol
concentration in the chilled
water circuit if glycol presence is
required
Check operational set points and
performance
• Calibrate controls
Check operation of all safety
devices
Inspect contacts and tighten
terminals
Megger the motor compressor
windings
Record operating pressures,
temperatures, amperages and
voltage
Carry out leak test
Check configuration of unit control
module
Change the oil as required based
upon results of the oil analysis
made during seasonal shutdown.
Get the 8 condition measurements at
the same time, on each circuit.
• HP
• LP
• Suction temperature
• Discharge temperature
• Liquid temperature
Water entering temperature
Water leaving temperature
Outdoor ambient temperature
Then calculate the sub-cooling and
superheat. No diagnosis can be
accurate with one of these records
missing.
Check operation of machines/
compare conditions of operation
against original commissioning
data.
Fill out the visit log sheet and
review with the operator