CG-SVX06F-GB36
General Start-up
In case of application with negative
temperature at the evaporator,
combination of simultaneous usage
of glycol both in evaporator and
condenser, or usage of another type
of fluid: please contact your local
Trane sales representative. A relief
valve is located at pump suction
limiting water circuit pressure at
3 bar. Nitrogen pressure inside of the
expansion tank must be equal to the
geometric height of the installation +
0.5 bar (in order to avoid air entering
in the water circuit). Expansion
tank must be inflated with nitrogen.
Pressure must be checked yearly. For
a good pump operation, pump suction
pressure must be between 0.5 and
2.5 bar when pump runs.